  MB_MASTER_INIT_TCP - configure the L02 built-in Ethernet port as a
  Modbus TCP master (client).

  While xInit is TRUE:
    R23812 := iTcpPort  Modbus TCP port (0 keeps the current port, 502)
    D8325  := iServers  number of remote servers (clamped to 1..4)
    D8395  := 4         Modbus TCP master (client)

  The body is level-triggered on purpose - pass a one-scan pulse as
  xInit, e.g. M0 := MB_MASTER_INIT_TCP(MEP(xApplyIp), 502, 1);
  Never tie xInit to TRUE.

  The IP addresses - PLC address, mask, gateway and the remote servers -
  are written with L02_SET_IP (Utils library). That function sets M8197,
  which applies R23812/D8325/D8395 together with the addresses and
  restarts the interface, so call MB_MASTER_INIT_TCP before the
  L02_SET_IP writes of the same scan.

  Do not write D8395, D8325 or R23812 from the application when this
  function is used.
*)
IF xInit THEN
	IF iTcpPort > 0 THEN
		R23812 := iTcpPort; (* Modbus TCP port *)
	END_IF;

	IF iServers < 1 THEN
		D8325 := 1; (* at least one remote server *)
	ELSIF iServers > 4 THEN
		D8325 := 4; (* at most four remote servers *)
	ELSE
		D8325 := iServers;
	END_IF;

	D8395 := 4; (* Modbus TCP master (client) *)
END_IF;
MB_MASTER_INIT_TCP := xInit;