/** * @license * Copyright 2022-2026 Matter.js Authors * SPDX-License-Identifier: Apache-2.0 */ /*** THIS FILE IS GENERATED, DO NOT EDIT ***/ import { MatterDefinition } from "../MatterDefinition.js"; import { ClusterElement as Cluster, AttributeElement as Attribute, FieldElement as Field, EventElement as Event, DatatypeElement as Datatype } from "../../elements/index.js"; export const PumpConfigurationAndControl = Cluster( { name: "PumpConfigurationAndControl", id: 0x200, classification: "application" }, Attribute({ name: "ClusterRevision", id: 0xfffd, type: "ClusterRevision", default: 5 }), Attribute( { name: "FeatureMap", id: 0xfffc, type: "FeatureMap" }, Field({ name: "PRSCONST", conformance: "O.a+", constraint: "0", title: "ConstantPressure" }), Field({ name: "PRSCOMP", conformance: "O.a+", constraint: "1", title: "CompensatedPressure" }), Field({ name: "FLW", conformance: "O.a+", constraint: "2", title: "ConstantFlow" }), Field({ name: "SPD", conformance: "O.a+", constraint: "3", title: "ConstantSpeed" }), Field({ name: "TEMP", conformance: "O.a+", constraint: "4", title: "ConstantTemperature" }), Field({ name: "AUTO", conformance: "O", constraint: "5", title: "Automatic" }), Field({ name: "LOCAL", conformance: "O", constraint: "6", title: "LocalOperation" }) ), Attribute( { name: "MaxPressure", id: 0x0, type: "int16", access: "R V", conformance: "M", default: null, quality: "X F" } ), Attribute( { name: "MaxSpeed", id: 0x1, type: "uint16", access: "R V", conformance: "M", default: null, quality: "X F" } ), Attribute({ name: "MaxFlow", id: 0x2, type: "uint16", access: "R V", conformance: "M", default: null, quality: "X F" }), Attribute({ name: "MinConstPressure", id: 0x3, type: "int16", access: "R V", conformance: "PRSCONST, [AUTO]", default: null, quality: "X F" }), Attribute({ name: "MaxConstPressure", id: 0x4, type: "int16", access: "R V", conformance: "PRSCONST, [AUTO]", default: null, quality: "X F" }), Attribute({ name: "MinCompPressure", id: 0x5, type: "int16", access: "R V", conformance: "PRSCOMP, [AUTO]", default: null, quality: "X F" }), Attribute({ name: "MaxCompPressure", id: 0x6, type: "int16", access: "R V", conformance: "PRSCOMP, [AUTO]", default: null, quality: "X F" }), Attribute({ name: "MinConstSpeed", id: 0x7, type: "uint16", access: "R V", conformance: "SPD, [AUTO]", default: null, quality: "X F" }), Attribute({ name: "MaxConstSpeed", id: 0x8, type: "uint16", access: "R V", conformance: "SPD, [AUTO]", default: null, quality: "X F" }), Attribute({ name: "MinConstFlow", id: 0x9, type: "uint16", access: "R V", conformance: "FLW, [AUTO]", default: null, quality: "X F" }), Attribute({ name: "MaxConstFlow", id: 0xa, type: "uint16", access: "R V", conformance: "FLW, [AUTO]", default: null, quality: "X F" }), Attribute({ name: "MinConstTemp", id: 0xb, type: "int16", access: "R V", conformance: "TEMP, [AUTO]", constraint: "min -27315", default: null, quality: "X F" }), Attribute({ name: "MaxConstTemp", id: 0xc, type: "int16", access: "R V", conformance: "TEMP, [AUTO]", constraint: "min -27315", default: null, quality: "X F" }), Attribute({ name: "PumpStatus", id: 0x10, type: "PumpStatusBitmap", access: "R V", conformance: "O", constraint: "desc", default: 0 }), Attribute({ name: "EffectiveOperationMode", id: 0x11, type: "OperationModeEnum", access: "R V", conformance: "M", constraint: "desc", quality: "N" }), Attribute({ name: "EffectiveControlMode", id: 0x12, type: "ControlModeEnum", access: "R V", conformance: "M", constraint: "desc", quality: "N" }), Attribute({ name: "Capacity", id: 0x13, type: "int16", access: "R V", conformance: "M", default: null, quality: "X" }), Attribute({ name: "Speed", id: 0x14, type: "uint16", access: "R V", conformance: "O", default: null, quality: "X" }), Attribute({ name: "LifetimeRunningHours", id: 0x15, type: "uint24", access: "RW VM", conformance: "O", default: 0, quality: "X N" }), Attribute({ name: "Power", id: 0x16, type: "uint24", access: "R V", conformance: "O", default: null, quality: "X" }), Attribute({ name: "LifetimeEnergyConsumed", id: 0x17, type: "uint32", access: "RW VM", conformance: "O", default: 0, quality: "X N" }), Attribute({ name: "OperationMode", id: 0x20, type: "OperationModeEnum", access: "RW VM", conformance: "M", constraint: "desc", default: 0, quality: "N" }), Attribute({ name: "ControlMode", id: 0x21, type: "ControlModeEnum", access: "RW VM", conformance: "O", constraint: "desc", default: 0, quality: "N" }), Attribute({ name: "AlarmMask", id: 0x22, type: "uint16", conformance: "D" }), Event({ name: "SupplyVoltageLow", id: 0x0, access: "V", conformance: "O", priority: "info" }), Event({ name: "SupplyVoltageHigh", id: 0x1, access: "V", conformance: "O", priority: "info" }), Event({ name: "PowerMissingPhase", id: 0x2, access: "V", conformance: "O", priority: "info" }), Event({ name: "SystemPressureLow", id: 0x3, access: "V", conformance: "O", priority: "info" }), Event({ name: "SystemPressureHigh", id: 0x4, access: "V", conformance: "O", priority: "info" }), Event({ name: "DryRunning", id: 0x5, access: "V", conformance: "O", priority: "critical" }), Event({ name: "MotorTemperatureHigh", id: 0x6, access: "V", conformance: "O", priority: "info" }), Event({ name: "PumpMotorFatalFailure", id: 0x7, access: "V", conformance: "O", priority: "critical" }), Event({ name: "ElectronicTemperatureHigh", id: 0x8, access: "V", conformance: "O", priority: "info" }), Event({ name: "PumpBlocked", id: 0x9, access: "V", conformance: "O", priority: "critical" }), Event({ name: "SensorFailure", id: 0xa, access: "V", conformance: "O", priority: "info" }), Event({ name: "ElectronicNonFatalFailure", id: 0xb, access: "V", conformance: "O", priority: "info" }), Event({ name: "ElectronicFatalFailure", id: 0xc, access: "V", conformance: "O", priority: "critical" }), Event({ name: "GeneralFault", id: 0xd, access: "V", conformance: "O", priority: "info" }), Event({ name: "Leakage", id: 0xe, access: "V", conformance: "O", priority: "info" }), Event({ name: "AirDetection", id: 0xf, access: "V", conformance: "O", priority: "info" }), Event({ name: "TurbineOperation", id: 0x10, access: "V", conformance: "O", priority: "info" }), Datatype( { name: "PumpStatusBitmap", type: "map16" }, Field({ name: "DeviceFault", conformance: "M", constraint: "0" }), Field({ name: "SupplyFault", conformance: "M", constraint: "1" }), Field({ name: "SpeedLow", conformance: "M", constraint: "2" }), Field({ name: "SpeedHigh", conformance: "M", constraint: "3" }), Field({ name: "LocalOverride", conformance: "M", constraint: "4" }), Field({ name: "Running", conformance: "M", constraint: "5" }), Field({ name: "RemotePressure", conformance: "M", constraint: "6" }), Field({ name: "RemoteFlow", conformance: "M", constraint: "7" }), Field({ name: "RemoteTemperature", conformance: "M", constraint: "8" }) ), Datatype( { name: "OperationModeEnum", type: "enum8" }, Field({ name: "Normal", id: 0x0, conformance: "M" }), Field({ name: "Minimum", id: 0x1, conformance: "SPD" }), Field({ name: "Maximum", id: 0x2, conformance: "SPD" }), Field({ name: "Local", id: 0x3, conformance: "LOCAL" }) ), Datatype( { name: "ControlModeEnum", type: "enum8" }, Field({ name: "ConstantSpeed", id: 0x0, conformance: "SPD" }), Field({ name: "ConstantPressure", id: 0x1, conformance: "PRSCONST" }), Field({ name: "ProportionalPressure", id: 0x2, conformance: "PRSCOMP" }), Field({ name: "ConstantFlow", id: 0x3, conformance: "FLW" }), Field({ name: "ConstantTemperature", id: 0x5, conformance: "TEMP" }), Field({ name: "Automatic", id: 0x7, conformance: "AUTO" }) ) ); MatterDefinition.children.push(PumpConfigurationAndControl);